Main Technyske spesifikaasje

 

Rated Voltage

KV

12

Rated Aktueel

IN

630/1250

Rated Frequency

Hz

50

Koarte tiid macht-frekwinsje wjerstean spanning (1min)

KV

48

Rated wjerljocht ympuls wjerstân spanning (piek)

KV

75

Rated Short-circuit Brenking Strom

DE

25/31.5

Rated Peak Standert Strom

DE

63/80

Rated Kortsluting Making Strom

DE

63/80

Rated Koarte tiid Standert Strom

DE

25/31.5

Rated Duration of Short-circ

S

4

Rated Single Capacitor Bank Breaking Current

IN

400

Rated Back to Back Capacitor Bank Breaking Current

IN

400

Rated Kortsluting Making Strom

Times

20

Massa fan bewegende dielen

Kg

2.5

Mechanyske Endurance

Times

10000

Kontakt sluten krêft fanwege balgen en sfear

N

110±30

Tsjinkrêft fan Kontakt by Full Stroke

N

210±30

Circuit Resistance at Min.Rated Contact Force

20

Kontakt Limit Erosion

mm

3

Storage Life

Jierren

20

Grutte fan partiel ûntslach (13.2KV)

PC

≤1

Torsionproof Moment Of Bellows

Nm

≤45

 

Mechanyske gegevens fan fakuüm switch foarsjoen fan de interrupters

 

Ferljochting tusken iepen kontakten

mm

9±1

Gemiddelde iepening snelheid

m/s

1,4±0,2

Gemiddelde slutingssnelheid

m/s

0,7±0,2

Rated Contact Pressure

N

3200±200

Kontakt Bounce Duration by Closing Operation

ms

Ut de simultaneens fan kontakt sluten en operaasje

ms

Maksimum rebound tidens iepening

mm

 

 

 

it giet

Notysjes

1. Voldoet of grutter de easken foar elektryske úthâldingsfermogen fan klasse E2 foar autoreclosing plicht neffens IEC62271-100 en GB1984-2003

2. Rated skaaimerken te jaan op oanfraach.