Notysjes
1. Moetet of grutter de elektryske úthâldingsfermogen easken fan klasse E2 foar autoreclosing plicht per IEC62271-100 en GB1984-2003.
2. Rated skaaimerken te jaan op oanfraach.
3. Rated isolaasje wearden easkje eksterne isolaasje, lykas Sf6, oalje of bêst dielectric materiaal ensfh
Main Technyske spesifikaasje
Rated Voltage | KV | 12 |
Rated Aktueel | IN | 1250 |
Rated Frequency | Hz | 50 |
Koarte tiid macht-frekwinsje wjerstean spanning (1min) | KV | 42/48 |
Rated wjerljocht ympuls wjerstân spanning (piek) | KV | 85 |
Rated Short-circuit Brenking Strom | DE | 31.5 |
Rated Peak Standert Strom | DE | 80 |
Rated Kortsluting Making Strom | DE | 80 |
Rated Koarte tiid Standert Strom | DE | 31.5 |
Rated Duration of Short-circ | S | 4 |
Rated Single Capacitor Bank Breaking Current | IN | 400 |
Rated Back to Back Capacitor Bank Breaking Current | IN | 400 |
Rated Kortsluting Making Strom | Times | 20 |
Massa fan bewegende dielen | Kg | 1.2 |
Mechanyske Endurance | Times | 10000 |
Kontakt sluten krêft fanwege balgen en sfear | N | 110±30 |
Tsjinkrêft fan Kontakt by Full Stroke | N | 210±30 |
Circuit Resistance at Min.Rated Contact Force | mΩ |
|
Kontakt Limit Erosion | mm | 3 |
Storage Life | Jierren | 20 |
Mechanyske gegevens fan fakuüm switch foarsjoen fan de interrupters
Ferljochting tusken iepen kontakten | mm | 9±1 |
Gemiddelde iepening snelheid | m/s | 1,4±0,2 |
Gemiddelde slutingssnelheid | m/s | 0,7±0,2 |
Rated Contact Pressure | N | 3200±200 |
Kontakt Bounce Duration by Closing Operation | ms |
|
Ut de simultaneens fan kontakt sluten en operaasje | ms |
|
Maksimum rebound tidens iepening | mm |
|